When it comes to solar interconnections, one phrase makes every designer pause — “supply-side tap.”
It’s a powerful solution that allows large PV systems to connect directly to the service conductors ahead of the main breaker, but it also comes with strict NEC rules, AHJ interpretations, and utility constraints.
Let’s break down what a supply-side tap really is, when to use it, and how to avoid common design and inspection failures that cost contractors time and money.
1. What Is a Supply-Side Tap?
A supply-side connection (also called line-side tap) connects the solar system before the main service disconnect — directly into the utility service conductors.
This allows the PV system to bypass the main breaker limitation (120% rule under NEC 705.12(D)) and is often used for:
- Large residential systems exceeding panel capacity
- Commercial installations where service upgrades are expensive
- Utility interconnections requiring separate metering
2. NEC Code References You Must Know
NEC Article | Requirement |
705.11 (2020 NEC) | Governs supply-side (line-side) interconnections |
230.82(6) | Allows additional disconnects (PV systems) on the supply side |
230.46 | Requires listed connectors and equipment for taps |
230.70(A)(1) | Location of disconnects — readily accessible and grouped |
250.24(C) | Neutral bonding and grounding specifics for service connections |
Pro Tip: Always confirm your AHJ’s adopted NEC year — older jurisdictions may still operate under 2017 NEC, where numbering and rules differ.
3. Types of Supply-Side Taps
A. Service Lug Tap (Meter Base Tap)
- Tap installed at meter base using listed lugs or “split-bolt” style connectors.
- Must maintain enclosure listing.
- Ideal for single-family systems under 15kW.
B. Gutter Tap (Service Raceway Tap)
- Conductors tapped inside a service gutter or trough before the main disconnect.
- Common for commercial and multifamily systems.
- Must ensure spacing and tap length limits per NEC 240.21(B).
C. Main Service Panel Tap
- Connection made at panel bus or service conductors feeding the main breaker.
- Requires UL-listed tap kits (e.g., Milbank, Eaton, or Ilsco).
- Verify with manufacturer instructions and AHJ approval.
4. Design Best Practices
To ensure safe, code-compliant design:
-
Use Listed Connectors Only
- Split bolts or mechanical lugs must be UL 486A/B listed.
- No “field-drilled” or modified bus bars.
-
Tap Conductor Protection
- Size per NEC 240.21(B) and protect with overcurrent device as close as possible.
- For most cases, 10 feet max tap length applies.
-
Grounding and Bonding
- Neutral and equipment grounds must not be bonded downstream of the service disconnect.
- Use bonding bushings where metallic conduits pass between enclosures.
-
Accessible Disconnect Location
- PV disconnect must be readily accessible and grouped with utility service disconnect.
- Clearly labeled with “PV SUPPLY DISCONNECT”.
-
Labeling
- NEC 705.10: “Power Source Output Connection – Do Not Relocate This Connection.”
- NEC 110.21(B): Permanent, UV-rated, reflective labels only.
5. Common Inspection Red Flags
AHJ inspectors commonly flag these issues during line-side tap inspections:
Unlisted connectors — field-made or improvised tap points.
No protective raceway — tap conductors exposed between enclosures.
Improper labeling — missing NEC article reference or directional current marking.
Bonding violations — neutral bonded at multiple locations.
Access issues — disconnects hidden behind equipment or fencing.
Each red flag means one more re-inspection, one more week lost, and possibly utility rejection.
6. Utility Coordination Tips
Even if your tap passes NEC inspection, the utility company may still deny it if:
- The service conductors are utility-owned (common in meter stacks).
- The meter base modification voids utility approval.
- Multiple generation sources (e.g., battery + PV) aren’t properly documented.
Always include:
- Utility interconnection diagram
- Tap photo reference sheet
- Equipment data sheets
- Service layout page showing tap location and disconnect grouping
7. Documentation Standards (AHJ + Utility)
Your permit drawing set should include:
- Detailed tap diagram with labeled conductor sizes
- Tap point photo (for as-built reference)
- NEC code callouts next to each note
- Grounding diagram showing neutral isolation and GEC path
- Clear label sheet with every disconnect and junction point
This not only satisfies AHJ inspectors but also gives utilities confidence in your work.
8. When to Avoid Supply-Side Taps
Use caution or avoid supply-side taps when:
- Service conductors are aluminum and hard to access
- The utility does not permit meter modifications
- The main service is inside a sealed or multi-tenant enclosure
- The PV system is under 10kW (breaker backfeed is easier and cheaper)
In these cases, load-side interconnection under the 120% rule is often simpler and faster.
Conclusion
Supply-side taps are a powerful tool for solar designers, but they require precision and documentation discipline.
When done right, they unlock larger system capacities and avoid costly service upgrades.
When done wrong, they trigger inspection failures, red tags, and rework.
Understanding NEC 705.11, following manufacturer listings, and designing with clarity will make your next AHJ review effortless.
Need supply-side tap drawings, grounding diagrams, and AHJ-ready documentation?
Vishtik’s Permit Design Team specializes in utility-compliant interconnection drawings that pass inspection the first time.
Get your project reviewed by experts who’ve seen it all — from NEC redlines to AHJ approvals.